| IN STOCK SERIES: | |
|---|---|
| ALTERNATE RELAY DUPLEXORS | ARA & ARB Series |
| AC GO/NO-GO CURRENT MONITOR/RELAYS | CMB Series CMG Series |
| AC OVER CURRENT MONITOR/RELAYS | CMO Series |
| AC UNDER CURRENT MONITOR/RELAYS | CMU Series |
| PHASE LOSS, UNDER VOLTAGE & PHASE SEQUENCE MONITOR/RELAYS | SLA Series |
| MICROPROCESSOR CONTROLLED THREE PHASE MONITOR/RELAYS | SLM Series |
| DELAY ON OPERATE/DELAY ON RELEASE (RELAY OUTPUT) | TDJ Series |
| INTERVAL ON OPERATE (RELAY OUTPUT) | TBB Series |
| TRUE DELAY ON RELEASE (RELAY OUTPUT) | TDT Series |
| UNITIMER PROGRAMMABLE TIME DELAY RELAY (RELAY OUTPUT) | TDU Series |
| SINGLE PHASE UNDER VOLTAGE MONITOR/RELAYS | UOA Series |
| SINGLE CHANNEL ISOLATION SWITCHES | ISO Series |
| OCTAL RELAY SOCKETS | RB08 RB11 |

| Specifications | |
|---|---|
| Control Voltage: | 24, 120 VAC/DC, 208, 240 VAC, 50/60Hz, 48 VDC, ±10% |
| Control Switch Current: | 1 mA |
| Contact Rating: | 10 Amps @ 240 VAC Resistive 1/8 hp @ 120 VAC 1/4 hp @ 240 VAC Inductive 360 VA @ 240 VAC, Inductive |
| Power Required: | 3 VA (Approximately) |
| Temperatures: | Operate: –20°C to +55°C Storage: –45°C to +85°C |
| Duty Cycle: | Continuous |
| Life Expectancy: | Mechanical: 10,000,000 Operations (Minimum) Electrical: 100,000 Operations @ Rated Load |
| Indicators: | LED Shows Output Position |
| Enclosure Style: | ‘A’ Lexan® Dust Cover |
| Terminations: | Industrial Plug-in |
| Agency Approval: | UL and Canadian UL; Recognition; File #E55826 |

| Specifications | |
|---|---|
| Control Voltage: | 24 or 120 VAC; 50/60 Hz, 24 VDC |
| AC Input Current: | Up to 50 Amps |
| Trip Point: | 1–10 Amps, Fixed |
| Response Times: | Operate: 30 Milliseconds Release: 0.5 Seconds |
| Temperatures: | Operate: 0°C to +55°C Storage: –45°C to +85°C |
| Power Consumption: | 3 Watts (Approximately) |
| Output: | SPDT, 10 Amps @ 240 VAC Resistive 211 VA @ 120 VAC Inductive 1/6 Horsepower @ 120 VAC or 1/3 Horsepower @ 240 VAC |
| Life Expectancy: | Mechanical: 10 Million Operations (Minimum) Electrical: 100,000 Operations @ Rated Load |
| Duty Cycle: | Continuous |
| Enclosure: | Lexan Dust Cover; 8 pin plug-in |
| Agency Approval: | UL Recognized: |
| Canadian Recognized: | File #E5582624 VDC not recognized |

| Specifications | |
|---|---|
| Control Voltage: | Not Required |
| Trip Points: | Pick up: Depends on Model. Request more info. Drop Out: 25% below pick up |
| Hysteresis: | 25% |
| Response Times: | Operate: 400mSec. (Approximately) Release: 50mSec. (Approximately) |
| Temperatures: | Operate: 0°C to +55°C Storage: –45°C to +85°C |
| Output: | SPST - N.O., 5 Amps @ 240 VAC, Resistive |
| Accuracy: | ±5% on Pick-up |
| Reset: | Automatic |
| Enclosure: | Style “D” Surface Mounted |
| Terminations: | (2) 1/4" Quick Disconnect Terminals |
| Agency Approval: | UL Recognized |
| Canadian Recognized: | File #E55826 |

| Specifications | |
|---|---|
| Control Voltage: | 24 or 120 VAC/VDC; 50/60 Hz |
| Trip Points: | Pick up: Depends on Model. Request more info. Drop out: 5% below pick up |
| Hysteresis: | 5% |
| Response Times: | Operate: 0.1 to 5 Seconds, Adjustable Release: 0.2 Seconds |
| Temperatures: | Operate: 0 C to +55 C Storage: 45 C to +85 C |
| Reset: | Automatic |
| Output: | DPDT, 10 Amps @ 120 VAC, Resistive |
| Indicator: | LED Glows On Over Current (Style E Enclosure Only) |
| Enclosure: | Style A: Lexan Dust Cover; 11-pin Plug-in Style E: Lexan Surface Mounted:#8-32 Screw Terminals |
The CMU Series is used to detect under current conditions. The internal relay is energized (pick up) when the monitored current is above the preset trip point. The relay de-energizes (drop out) when the current falls below the trip point for longer than the adjustable delay. The delay is incorporated to prevent nuisance tripping caused by momentary line dips. The relay re-energizes when the current rises 5% above the drop out trip point for longer than 0.1 seconds. The relay has the automatic reset feature. An external CT may be used to extend the range of the Current Monitor.| Specifications | |
|---|---|
| Control Voltage: | 24 or 120 VAC, 50/60 Hz; 24 VDC |
| Trip Points: | Pick up: 5% above drop out Drop out: Depends on Model. Order more info. |
| Hysteresis: | 5% |
| Response Times: | Operate: 0.1 Seconds Release: 0.1 to 5 Seconds, Adjustable |
| Temperatures: | Operate: 0°C to +55°C Storage: –45°C to +85°C |
| Reset: | Automatic |
| Output: | DPDT, 10 Amps @ 120 VAC, Resistive |
| Indicator: | Glows When Current is Above Preset Current Trip Point (Style E Enclosure Only) |
| Enclosure: | Style A: Lexan Dust Cover; 11-pin Plug-in Style E: Lexan Surface Mounted: #8-32 Screw Terminals |

| Specifications: | |
|---|---|
| Dropout Voltage: | 1 Ø Low: 83% of Nominal3 Ø Low: 90% of Nominal |
| Response Times: | Models Up to 300 VAC Operate: 250 Milliseconds Release: 0.5 Seconds Models Over 300 VAC |
| Operate: 1.0 Seconds Release: 2.0 Seconds | |
| Temperatures: | Operate: 0°C to +55°CStorage: -45°C to +85°C |
| Phase Sequence: | ABC (Will Not Operate CBA) |
| U.S. Patent Number: | 3,611,050 |

| Protects Against | Features |
| PHASE LOSS | FAULT INDICATORS |
| UNDER VOLTAGE | EXTERNAL ADJUSTMENTS |
| OVER VOLTAGE | AUTO/MANUAL RESET |
| PHASE UNBALANCE | DELAY-ON-MAKE |
| PHASE REVERSAL | LAST FAULT MEMORY |
| FREQUENCY SHIFT | DPDT CONTACTS |
| PHASE SHIFT LOW | POWER CONSUMPTION |
| UNIFORM RESTART IN MULTIPLE LOAD INSTALLATIONS | COMPACT PACKAGING |
| Specifications: | |
|---|---|
| Phase Sequence: | ABC (Will Not Operate CBA) |
| Voltage Trip Points: | Drop -Out: ±10% of Setting Pickup: ±7% of Setting |
| Frequency Trip Points: | Dropout: ±4% of 60 Hz (380 V, 50 Hz) Pickup ±3% of 60 Hz (380 V, 50 Hz) |
| Unbalance Trip Points: | Dropout: 7%Pickup: 5% |
| Output Rating: | DPDT, 360 VA Inductive; 1/2 hp 3 A Resistive @ 600 VAC |
| Response Times Operate: | Sampling: 2 Seconds Delay-on-make: (Sampling Delay) + (1.5 seconds to 5 minutes Delay). Adjustable in one (1) minute increments |
| Release: | Under/Over Voltage & Frequency Shift:1.5 Seconds, (Approx.) Unbalance: 2.0 Seconds, (Approx.) Phase Loss/Shift: 1.0 Seconds, (Approx.) |
| Reset Modes: | Automatic; Manual; Automatic w/Memory |
| LED Indicators: | Green/Red |
| Power Required: | 7 VA Typical |
| Transient Withstand: | 2500 Volts for 10 ms |
| Temperatures: | Operate: 0°C to + 55°C Storage: -45°C to +85°C |
| Enclosure: | Lexan Surface Mounted |
| Terminations: | #8-32 Screw Terminals |
| Agency Approvals: | UL Listed: File #E55826; CSA Certified; File #LR40123 |
Voltage is continuously applied to the input. An external isolated switch controls the timer. When closed, the Delay On Operate delay T1 begins. Upon completion, the relay energizes. When the switch opens, the Delay on Release delay T2 begins. Upon completion, the relay de-energizes and the cycle is complete. Reset is accomplished by reclosing the control switch after the timing cycle has completed. If the switch opens during the Delay on Operate mode, the relay will remain de-energized and T1 will reset. If the switch is reclosed during the Delay on Release mode, the relay will remain energized and T2 will reset. Both delay periods are independently adjustable.| Specifications | |
|---|---|
| Supply Voltages: | 24 or 120 volts, AC 50/60 Hz, or DC; –10% |
| Timing Ranges: | Virtually unlimited. |
| Timing Tolerances: | Minimum Setting: +0 20% Maximum Setting: –10% |
| Repeatability: | 1% maximum; no first cycle effect |
| Output Rating: | DPDT, 10 Amps @ 250 VAC or 24 VDC, Resistive 211 VA @ 120 VAC, Inductive |
| Temperatures: | Operate: 0° C to +55° C Storage: 45° C to +85° C |
| Reset Times: | Before Time Out: 100 m. seconds After Time Out: 50 m. seconds |
| Recycle Time: | 40 m. seconds |
| False Transfer: | No |
| Reverse Polarity Protected: | Yes |
| Power Consumption: | 3 watts (approx.) |
| Life Expectancy: | Mechanical: 10 Million Operations (min.) Electrical: 100,000 Operations @ Rated Load |
| Agency Approval: | UL Recognized; File #E55826 |
When control voltage is applied to the input terminals, the relay energizes and the time delay begins. Upon completion of the delay period, the relay de-energizes. Reset during or after the delay period is accomplished by removal of the control voltage.| Specifications | |
|---|---|
| Control Voltage: | 12, 24, 48, 120, or 240 volts AC, 50/60 Hz, or DC ±10% |
| Time Delay Range: | Order More Info |
| Accuracies: | Setting: ±2% or ±50 Milliseconds Whichever is Greater Repeat: 60.1% or ±8.3 Milliseconds Whichever is Greater |
| Reset Time: | Before Time Out: 100 m. seconds After Time Out: 50 m. seconds |
| Output: | 10 Amps @ 250 VAC or 24 VDC, Resistive |
| Temperatures: | Operate: 0°C to +55°C Storage: –45°C to +85°C |
| False Transfer: | No |
| Reverse Polarity Protected: | Yes |
| Power Consumption: | 3 watts (approximately) |
| Duty Cycle: | Continuous |
| Life Expectancy: | Mechanical: 10 Million Operations (minimum) Electrical: 100,000 Operations @ Rated Load |
| Indicators: | LED Glows when Relay is Energized |
| Isolation: | 1,500 Volts, Input/Output |
| Agency Approvals: | UL Recognized; File #E55826 CSA Certified; File #LR40123 |
When voltage is applied to the input terminals, the relay energizes. When voltage is removed, the OFF delay begins. Upon completion of the delay period, the relay de-energizes. Reset is accomplished by reapplying voltage to the input terminals.| Specifications | |
|---|---|
| Supply Voltages: | 24, 110/120 or 208/240 volts, AC 50/60 Hz, or DC; and 48 volts DC; +10% |
| Timing Ranges: | Up to 300 seconds |
| Timing Tolerances: | Minimum setting: +0 – 20%Maximum Setting: ±10% |
| Repeatability: | 1% |
| Output Rating: | DPDT, 10 Amps,1/6 HP @ 240 VAC; 211 VA @ 120 VAC, Inductive |
| Temperatures: | Operate: 0°C to +55°CStorage: –45°C to +85°C |
| Reset: | 0.5 seconds |
| False Transfer: | No |
| Reverse Polarity Protected: | Yes |
| Power Consumption: | 3 watts (approx.) |
| Life Expectancy: | Mechanical: 10 Million Operations (min.)Electrical: 100,000 Operations @ RatedLoad |
| Agency Approval: | UL recognized; File #E55826 |
The TDU Series is the most versatile single timer available today. One (1) model replaces forty (40) industry standard devices: four (4) wide delay ranges x five (5) most common modes of operation x two (2) supply voltages — since they will operate on both AC and DC.The CMOS digital circuitry provides high accuracy, repeatability and fast reset times. The heavy-duty relays are rated for continuous operation at 10 amps. All programming is easily accomplished externally by using one or more jumpers between signated base pins — no trap doors to open, no switches to set, no disassembly required.| Specifications | |
|---|---|
| Supply Voltages: | 24, 120 or 240 volts AC, 50/60 Hz 12, 24, 48 or 110 volts, DC; ±10% |
| Operating Modes: | 1. Interval on Operate 2. Delay on Operate 3. Delay on Release 4. Single Shot 5. Flasher |
| Timing Ranges: | 1. 0.15 to 15 seconds 2. 0.6 to 60 seconds 3. 5 to 480 seconds 4. 0.6 to 64 minutes |
| Timing Tolerances: | Minimum Setting: +0 – 20% Maximum Setting: ±10% |
| Repeatability: | 0.1% typical; 0.5% maximum |
| Output Rating: | SPDT, 10 Amps @ 24 VDC or 250 VAC, Resistive 211 VA @ 120 VAC, Inductive |
| Temperatures: | Operate: 0°C to +55°C Storage: –45°C to +85°C |
| Reset Times: | Before Time Out: 100 m. seconds After Time Out: 50 m. seconds Recycle: 40 m. seconds |
| False Transfer: | No |
| Reverse Polarity Protected: | Yes |
| Power Consumption: | 3 watts (approx.) |
| Life Expectancy: | Mechanical: 10 Million Operations (min.) Electrical: 100,000 Operations @ Rated Load |
| Agency Approval: | UL Recognized; File #E55826 |
The UOA Series offers protection to single phase equipment that is required to operate above a certain voltage minimum. With Operating voltage applied above the preset pickup voltage, the internal relay will energize. When the voltage falls below the preset dropout voltage for a period longer than the release delay, the output relay will de-energize. When line conditions return above the preset pickup voltage, the UOA Series automatically resets and the internal relay energizes. The hysteresis in each unit provides a differential between the pickup and dropout trip points.| Specifications | |
|---|---|
| Response Times: | Operate: 50mSec. (Approx.) (500 mSec. on 12 VDC units) Release: 0.5 Seconds (Approx.) |
| Output Rating: | Style A - DPDT, 5A @ 240 VAC, Resistive: 211 VA @ 240, Inductive. Style N- SPDT, 10A @ 240 VAC, Resistive; 345 VA @ 240 VAC, Inductive. Style E - DPDT, 5A @ 240 VAC Resistive: 345 VA @ 240 VAC, Inductive. |
| Temperatures: | Operate: 0°C to +55°C Storage: -45°C to +85° |
| Power Required: | Models Up to 110 VDC: 3 Watts, Maximum Models Up to 300 VAC: 5 VA, Maximum Models Over 300 VAC: 5 VA, Maximum |
| Agency Approval: | UL Recognized File #E55826 |

Recommended for use with all 11-pin magnal plug-in devices. UL Recognized and CSA certified for 10 Amp @ 300 VAC. The molded thermoplastic base has brass, nickel plated inserts with #6-32 steel, nickel plated screws.
The ISO Series single channel devices are used to provide a safe and reliable means of controlling loads from hazardous locations without releasing sufficient energy, under normal or abnormal conditions, to cause ignition of a flammable or combustible atmospheric mixture while in its most easily ignited concentration. An isolated output turns on when the control switch input from the hazardous location is closed. When the control switch input opens, the isolated output turns off. The Style A single channel plug-in devices come equipped with integral spring mating clips which secure the device to the base make this unit the only UL913 Intrinsically Safe plug-in associated apparatus available on the market today. The Style N, surface mounted enclosure is sealed with a high quality epoxy resin material and has five (5) #8-32 screw terminals.| Specifications | |
|---|---|
| Control Voltage: | 24 or 120 VAC, ±10%, 50/60 Hz |
| Control Switch: | Open Circuit Voltage: 16 VDC Short Circuit Current: 200 uAmps |
| Contact Rating: | SPST-N.O., 10 amps @ 24 or 120 VAC, Resistive 278 VA, Inductive |
| Isolation: | 2500 volts, Input to Output |
| Power Required: | 1.5 VA |
| Temperatures: | Operate: –20°C to +55°C Storage: –40°C to +85°C |
| Response Times: | Operate: 6 mSeconds (Approx.) Release: 2.5 mSeconds (Approx.) |
| Life Expectancy: | Mechanical: 20 Million Operations Electrical: 50,000 Operations @ Rated Load |
| Duty Cycle: | Continuous |
| LED Indicator: | On When Output is On |
| Agency Approvals: | UL913 File #E151578; Class I, Groups A, B, C, D; Class II, Groups E, F, G; Class III, Hazardous Locations in ATC-DE; Drawing Nos. 191, 192 |