HomeAbout UsSearch Marsh InventoryProducts By CategoryLine CardServicesNewsHow To Order

ATC Diversified Electronics

RELAYS FROM ATC DIVERSIFIED ELECTRONICS IN STOCK AT
MARSH ELECTRONICS



Diversified Relays
For complete specifications and pricing on Diversified products listed here or for a catalog,
please give us a call (920) 757-0800 or (800) 877-8919, or send us an e-mail.
IN STOCK SERIES:
ALTERNATE RELAY DUPLEXORS ARA & ARB Series
AC GO/NO-GO CURRENT MONITOR/RELAYS CMB Series  CMG Series
AC OVER CURRENT MONITOR/RELAYS CMO Series
AC UNDER CURRENT MONITOR/RELAYS CMU Series
PHASE LOSS, UNDER VOLTAGE & PHASE SEQUENCE MONITOR/RELAYS SLA Series
MICROPROCESSOR CONTROLLED THREE PHASE MONITOR/RELAYS SLM Series
DELAY ON OPERATE/DELAY ON RELEASE (RELAY OUTPUT) TDJ Series
INTERVAL ON OPERATE (RELAY OUTPUT) TBB Series
TRUE DELAY ON RELEASE (RELAY OUTPUT) TDT Series
UNITIMER PROGRAMMABLE TIME DELAY RELAY (RELAY OUTPUT) TDU Series
SINGLE PHASE UNDER VOLTAGE MONITOR/RELAYS UOA Series
SINGLE CHANNEL ISOLATION SWITCHES ISO Series
OCTAL RELAY SOCKETS RB08  RB11
ARA/ARB Alternate Relay Duplexors

ARA & ARB SERIES ALTERNATE RELAY DUPLEXORS

The Duplexor is used in control panels where two loads are required to alternate to provide equal run time on the loads. The alternating action is initiated by a control switch, which is common with one side of the control voltage. The output contacts will change states each time the control switch is opened, thus alternating the two loads. The LED indicators show the position of the output relay. The ARA series is the standard Duplexor providing automatic alternating sequence. The ARB has the automatic sequencing feature plus the option of locking it into one sequence. A three position switch permits the field selection of normal duplexing action, locking in the A-B sequence, or B-A sequence.
Check Inventory

Specifications
Control Voltage:24, 120 VAC/DC, 208, 240 VAC,
50/60Hz, 48 VDC, ±10%
Control Switch Current:1 mA
Contact Rating:10 Amps @ 240 VAC
Resistive 1/8 hp @ 120 VAC
1/4 hp @ 240 VAC Inductive
360 VA @ 240 VAC, Inductive
Power Required:3 VA (Approximately)
Temperatures:Operate: –20°C to +55°C
Storage: –45°C to +85°C
Duty Cycle:Continuous
Life Expectancy:Mechanical: 10,000,000 Operations (Minimum)
Electrical: 100,000 Operations @ Rated Load
Indicators:LED Shows Output Position
Enclosure Style:‘A’ Lexan® Dust Cover
Terminations:Industrial Plug-in
Agency Approval:UL and Canadian UL; Recognition; File #E55826

CMB Series Current Monitor/Relays

AC Go/No-Go Current Monitor/Relays

CMB Series

The CMB Series relay is used to detect the presence of AC current. When the monitored current exceeds the trip point for longer than 30 milliseconds, the internal relay energizes. When the monitored current drops below the trip point for longer than 0.5 seconds, the internal relay de-energizes. The Delay-on-Release is incorporated to prevent nuisance tripping caused by momentary dips in the load line. An External CT may be used to extend the range of the Current Monitor.Features:
Check Inventory

Specifications
Control Voltage:24 or 120 VAC; 50/60 Hz, 24 VDC
AC Input Current:Up to 50 Amps
Trip Point:1–10 Amps, Fixed
Response Times:Operate: 30 Milliseconds
Release: 0.5 Seconds
Temperatures:Operate: 0°C to +55°C
Storage: –45°C to +85°C
Power Consumption:3 Watts (Approximately)
Output:SPDT, 10 Amps @ 240 VAC Resistive
211 VA @ 120 VAC Inductive
1/6 Horsepower @ 120 VAC or 1/3 Horsepower @ 240 VAC
Life Expectancy:Mechanical: 10 Million Operations (Minimum)
Electrical: 100,000 Operations @ Rated Load
Duty Cycle:Continuous
Enclosure:Lexan Dust Cover; 8 pin plug-in
Agency Approval:UL Recognized:
Canadian Recognized:File #E5582624 VDC not recognized

CMG Series Current Monitor/Relays

CMG SERIES

The CMG Series is a self powered Current Monitor/Relay that is used to detect the presence of AC current. When the monitored current exceeds the trip point for longer than 400 mSec., the internal relay energizes (pick up).When the monitored current drops below the trip point for longer than 50 mSec., the internal relay de-energizes (drop out). No physical connection is required as the line to be monitored is magnetically coupled by passing the conductor through the protruding Current Transformer of the monitor. No external supply is needed to power the monitor. The current trip point specified is with one turn through the transformer. Each time the number of turns through the transformer doubles, the trip point effectively halves. Example: CMG-0100-20 will trip at 20 amps with one turn passing through the transformer. By placing two turns through the transformer, the relay will trip at 10 amps. Likewise, four turns will cause the relay to trip at 5 amps.
Features:
Check Inventory

Specifications
Control Voltage:Not Required
Trip Points:Pick up: Depends on Model. Request more info.
Drop Out: 25% below pick up
Hysteresis:25%
Response Times:Operate: 400mSec. (Approximately)
Release: 50mSec. (Approximately)
Temperatures:Operate: 0°C to +55°C
Storage: –45°C to +85°C
Output:SPST - N.O., 5 Amps @ 240 VAC, Resistive
Accuracy:±5% on Pick-up
Reset:Automatic
Enclosure:Style “D” Surface Mounted
Terminations:(2) 1/4" Quick Disconnect Terminals
Agency Approval:UL Recognized
Canadian Recognized:File #E55826

CMO Series AC Over Current Monitor/Relays

CMO Series AC Over Current Monitor/Relays

The CMO Series is used to detect over current conditions. The internal relay energizes (pick up) when the monitored current exceeds the preset trip point for longer than the adjustable time delay. The delay is incorporated to prevent nuisance tripping caused by motor inrush currents. The CMO has an automatic reset feature. The internal relay de-energizes (drop out) when the current drops 5% below the preset trip for longer than 0.2 seconds. An External CT may be used to extend the range of the Current Monitor.
Check Inventory

Specifications
Control Voltage:24 or 120 VAC/VDC; 50/60 Hz
Trip Points:Pick up: Depends on Model. Request more info.
Drop out: 5% below pick up
Hysteresis:5%
Response Times:Operate: 0.1 to 5 Seconds, Adjustable
Release: 0.2 Seconds
Temperatures: Operate: 0 C to +55 C
Storage: 45 C to +85 C
Reset:Automatic
Output:DPDT, 10 Amps @ 120 VAC, Resistive
Indicator:LED Glows On Over Current (Style E Enclosure Only)
Enclosure:Style A: Lexan Dust Cover; 11-pin
Plug-in
Style E: Lexan Surface Mounted:#8-32 Screw Terminals

CMU Series AC Under Current Monitor/Relays

CMU Series AC Under Current Monitor/RelaysThe CMU Series is used to detect under current conditions. The internal relay is energized (pick up) when the monitored current is above the preset trip point. The relay de-energizes (drop out) when the current falls below the trip point for longer than the adjustable delay. The delay is incorporated to prevent nuisance tripping caused by momentary line dips. The relay re-energizes when the current rises 5% above the drop out trip point for longer than 0.1 seconds. The relay has the automatic reset feature. An external CT may be used to extend the range of the Current Monitor.
Check Inventory

Specifications
Control Voltage:24 or 120 VAC, 50/60 Hz; 24 VDC
Trip Points:Pick up: 5% above drop out
Drop out: Depends on Model. Order more info.
Hysteresis:5%
Response Times:Operate: 0.1 Seconds
Release: 0.1 to 5 Seconds, Adjustable
Temperatures:Operate: 0°C to +55°C
Storage: –45°C to +85°C
Reset:Automatic
Output:DPDT, 10 Amps @ 120 VAC, Resistive
Indicator:Glows When Current is Above Preset Current Trip Point (Style E Enclosure Only)
Enclosure:Style A: Lexan Dust Cover; 11-pin
Plug-in
Style E: Lexan Surface Mounted: #8-32 Screw Terminals
SLA Series Phase Loss Relays

SLA Series Phase Loss, Under Voltage and Phase Sequence Monitor/Relays

Diversified Phase Monitors operate independently of motor size or power requirements of the system. Some typical applications follow:
• Air Handlers      • Computer Power Protection
• Conveyor Drive      • Water Waste & Sewage Machinery
• Oil & Gas Pumps      • Sawmill & Woodpump Machinery
• Elevator Drives     • Robotics Equipment
• Automatic Transfer Switching for Irrigation Pumps Emergency Power Supplies
• Power Substation Monitoring      • Commercial/Industrial Air Conditioning
• Lift Station Pumps & Refrigeration Compressors

The SLA Series is designed to protect three-phase equipment against Phase Loss, Under Voltage, and Phase Reversal conditions. With normal operating voltages applied in the proper ABC sequence, the internal relay will energize (PICK-UP). When incorrect phase sequence or phase loss occurs or the three-phase voltages fall below the drop out voltages, the relay will de-energize (DROP-OUT). Both Delta and Wye systems may be monitored. In Wye systems, connections to neutral are not required. For UL Listed units, with field wiring terminals, copper wire with 60°/75°C rating must be used for control circuitry connections. On models featuring indicators, the LED glows when all line conditions are normal.
NOTE: When a phase is lost while the motor is running, a condition known as regeneration occurs where a voltage is induced into the open phase nearly equal in magnitude to the normal phase-to-phase voltage. However, with the exception of lightly loaded motors, enough change is detected by the SLA to provide the required protection when properly adjusted.
Check Inventory

Specifications:
Dropout Voltage:1 Ø Low: 83% of Nominal3 Ø Low: 90% of Nominal
Response Times:Models Up to 300 VAC Operate: 250 Milliseconds Release: 0.5 Seconds Models Over 300 VAC
Operate: 1.0 Seconds Release: 2.0 Seconds 
Temperatures:Operate: 0°C to +55°CStorage: -45°C to +85°C
Phase Sequence:ABC (Will Not Operate CBA)
U.S. Patent Number:3,611,050

SLM Series Microprocesor Controlled 3-Phase Monitor/Relays

SLM Series Microprocessor Controlled Three Phase Monitor/Relays

Protects AgainstFeatures
PHASE LOSSFAULT INDICATORS
UNDER VOLTAGEEXTERNAL ADJUSTMENTS
OVER VOLTAGEAUTO/MANUAL RESET
PHASE UNBALANCEDELAY-ON-MAKE
PHASE REVERSALLAST FAULT MEMORY
FREQUENCY SHIFTDPDT CONTACTS
PHASE SHIFT LOWPOWER CONSUMPTION
UNIFORM RESTART IN MULTIPLE LOAD INSTALLATIONSCOMPACT PACKAGING

Check Inventory

Specifications:
Phase Sequence:ABC (Will Not Operate CBA)
Voltage Trip Points:Drop -Out: ±10% of Setting
Pickup: ±7% of Setting
Frequency Trip Points:Dropout: ±4% of 60 Hz (380 V, 50 Hz)
Pickup ±3% of 60 Hz (380 V, 50 Hz)
Unbalance Trip Points:Dropout: 7%Pickup: 5%
Output Rating:DPDT, 360 VA Inductive; 1/2 hp 3 A Resistive @ 600 VAC
Response Times Operate:Sampling: 2 Seconds
Delay-on-make: (Sampling Delay) + (1.5 seconds to 5 minutes Delay). Adjustable in one (1) minute increments
Release:Under/Over Voltage & Frequency Shift:1.5 Seconds, (Approx.)
Unbalance: 2.0 Seconds, (Approx.)
Phase Loss/Shift: 1.0 Seconds, (Approx.)
Reset Modes:Automatic; Manual; Automatic w/Memory
LED Indicators: Green/Red
Power Required:7 VA Typical
Transient Withstand:2500 Volts for 10 ms
Temperatures:Operate: 0°C to + 55°C
Storage: -45°C to +85°C
Enclosure:Lexan Surface Mounted
Terminations:#8-32 Screw Terminals
Agency Approvals:UL Listed: File #E55826; CSA Certified; File #LR40123

TDJ Series Delay on Operate/Delay on Release (Relay Output)

TDJ Series Delay RelaysVoltage is continuously applied to the input. An external isolated switch controls the timer. When closed, the Delay On Operate delay T1 begins. Upon completion, the relay energizes. When the switch opens, the Delay on Release delay T2 begins. Upon completion, the relay de-energizes and the cycle is complete. Reset is accomplished by reclosing the control switch after the timing cycle has completed. If the switch opens during the Delay on Operate mode, the relay will remain de-energized and T1 will reset. If the switch is reclosed during the Delay on Release mode, the relay will remain energized and T2 will reset. Both delay periods are independently adjustable.
Check Inventory

Specifications
Supply Voltages:24 or 120 volts, AC 50/60 Hz, or DC; –10%
Timing Ranges:Virtually unlimited.
Timing Tolerances:Minimum Setting: +0 20%
Maximum Setting: –10%
Repeatability:1% maximum; no first cycle effect
Output Rating:DPDT, 10 Amps @ 250 VAC or 24 VDC, Resistive
211 VA @ 120 VAC, Inductive
Temperatures:Operate: 0° C to +55° C
Storage: 45° C to +85° C
Reset Times:Before Time Out: 100 m. seconds
After Time Out: 50 m. seconds
Recycle Time:40 m. seconds
False Transfer:No
Reverse Polarity Protected:Yes
Power Consumption:3 watts (approx.)
Life Expectancy:Mechanical: 10 Million Operations (min.)
Electrical: 100,000 Operations @ Rated Load
Agency Approval:UL Recognized; File #E55826

TBB Series Interval On Operate (Relay Output)

TBB Series Inverval On Operate RelaysWhen control voltage is applied to the input terminals, the relay energizes and the time delay begins. Upon completion of the delay period, the relay de-energizes. Reset during or after the delay period is accomplished by removal of the control voltage.
Digital selection of the time delay is accomplished by the use of ten (10) binary switches, each marked with a time increment. The time periods, of which there are five (5) ranges, represented by each switch in the ON position is added together to obtain the desired time delay. No more trial-by-error adjustments.
Check Inventory

Specifications
Control Voltage:12, 24, 48, 120, or 240 volts AC, 50/60 Hz, or DC ±10%
Time Delay Range:Order More Info
Accuracies:Setting: ±2% or ±50 Milliseconds Whichever is Greater
Repeat: 60.1% or ±8.3 Milliseconds Whichever is Greater
Reset Time:Before Time Out: 100 m. seconds
After Time Out: 50 m. seconds
Output:10 Amps @ 250 VAC or 24 VDC, Resistive
Temperatures:Operate: 0°C to +55°C
Storage: –45°C to +85°C
False Transfer:No
Reverse Polarity Protected:Yes
Power Consumption:3 watts (approximately)
Duty Cycle:Continuous
Life Expectancy:Mechanical: 10 Million Operations (minimum)
Electrical: 100,000 Operations @ Rated Load
Indicators:LED Glows when Relay is Energized
Isolation:1,500 Volts, Input/Output
Agency Approvals:UL Recognized; File #E55826 CSA Certified; File #LR40123

TDT Series True Delay on Release (Relay Output)

TDT Series True Delay On Release RelaysWhen voltage is applied to the input terminals, the relay energizes. When voltage is removed, the OFF delay begins. Upon completion of the delay period, the relay de-energizes. Reset is accomplished by reapplying voltage to the input terminals.
Check Inventory

Specifications
Supply Voltages:24, 110/120 or 208/240 volts, AC 50/60 Hz, or DC; and 48 volts DC; +10%
Timing Ranges:Up to 300 seconds
Timing Tolerances:Minimum setting: +0 – 20%Maximum Setting: ±10%
Repeatability:1%
Output Rating:DPDT, 10 Amps,1/6 HP @ 240 VAC; 211 VA @ 120 VAC, Inductive
Temperatures:Operate: 0°C to +55°CStorage: –45°C to +85°C
Reset:0.5 seconds
False Transfer:No
Reverse Polarity Protected:Yes
Power Consumption:3 watts (approx.)
Life Expectancy:Mechanical: 10 Million Operations (min.)Electrical: 100,000 Operations @ RatedLoad
Agency Approval:UL recognized; File #E55826

TDU Series – Unitimer Programmable Time Delay Relay (Relay Output)

TDU Series Unitimer Time Delay RelaysThe TDU Series is the most versatile single timer available today. One (1) model replaces forty (40) industry standard devices: four (4) wide delay ranges x five (5) most common modes of operation x two (2) supply voltages — since they will operate on both AC and DC.The CMOS digital circuitry provides high accuracy, repeatability and fast reset times. The heavy-duty relays are rated for continuous operation at 10 amps. All programming is easily accomplished externally by using one or more jumpers between signated base pins — no trap doors to open, no switches to set, no disassembly required.
Check Inventory

Specifications
Supply Voltages:24, 120 or 240 volts AC, 50/60 Hz
12, 24, 48 or 110 volts, DC; ±10%
Operating Modes:1. Interval on Operate
2. Delay on Operate
3. Delay on Release
4. Single Shot
5. Flasher
Timing Ranges:1. 0.15 to 15 seconds
2. 0.6 to 60 seconds
3. 5 to 480 seconds
4. 0.6 to 64 minutes
Timing Tolerances:Minimum Setting: +0 – 20%
Maximum Setting: ±10%
Repeatability:0.1% typical; 0.5% maximum
Output Rating:SPDT, 10 Amps @ 24 VDC or 250 VAC, Resistive
211 VA @ 120 VAC, Inductive
Temperatures:Operate: 0°C to +55°C
Storage: –45°C to +85°C
Reset Times:Before Time Out: 100 m. seconds
After Time Out: 50 m. seconds
Recycle: 40 m. seconds
False Transfer:No
Reverse Polarity Protected:Yes
Power Consumption:3 watts (approx.)
Life Expectancy:Mechanical: 10 Million Operations (min.)
Electrical: 100,000 Operations @ Rated Load
Agency Approval:UL Recognized; File #E55826

UOA Series Single Phase Under Voltage Monitor/Relays

UOA Series Single Phase Under Voltage Monitor/RelaysThe UOA Series offers protection to single phase equipment that is required to operate above a certain voltage minimum. With Operating voltage applied above the preset pickup voltage, the internal relay will energize. When the voltage falls below the preset dropout voltage for a period longer than the release delay, the output relay will de-energize. When line conditions return above the preset pickup voltage, the UOA Series automatically resets and the internal relay energizes. The hysteresis in each unit provides a differential between the pickup and dropout trip points.
Check Inventory

Specifications
Response Times:Operate: 50mSec. (Approx.) (500 mSec. on 12 VDC units)
Release: 0.5 Seconds (Approx.)
Output Rating:Style A - DPDT, 5A @ 240 VAC, Resistive: 211 VA @ 240, Inductive.
Style N- SPDT, 10A @ 240 VAC, Resistive; 345 VA @ 240 VAC, Inductive.
Style E - DPDT, 5A @ 240 VAC Resistive: 345 VA @ 240 VAC, Inductive.
Temperatures:Operate: 0°C to +55°C
Storage: -45°C to +85°
Power Required:Models Up to 110 VDC: 3 Watts, Maximum
Models Up to 300 VAC: 5 VA, Maximum
Models Over 300 VAC: 5 VA, Maximum
Agency Approval:UL Recognized File #E55826

OCTAL RELAY SOCKETS

RB08 Octal Relay Socket

RB08

Recommended for use with all 8 pin octal plug-in devices. UL Recognized and CSA Certified for 10 Amps @ 600 VAC. The molded thermoplastic base has brass, nickel plated inserts with #6-32 steel, nickel plated screws.

RB11

RB11 Octal Relay SocketRecommended for use with all 11-pin magnal plug-in devices. UL Recognized and CSA certified for 10 Amp @ 300 VAC. The molded thermoplastic base has brass, nickel plated inserts with #6-32 steel, nickel plated screws.

ISO Series Single Channel Isolation Switches

ISO Series Single Channel Isolation SwitchesThe ISO Series single channel devices are used to provide a safe and reliable means of controlling loads from hazardous locations without releasing sufficient energy, under normal or abnormal conditions, to cause ignition of a flammable or combustible atmospheric mixture while in its most easily ignited concentration. An isolated output turns on when the control switch input from the hazardous location is closed. When the control switch input opens, the isolated output turns off. The Style A single channel plug-in devices come equipped with integral spring mating clips which secure the device to the base make this unit the only UL913 Intrinsically Safe plug-in associated apparatus available on the market today. The Style N, surface mounted enclosure is sealed with a high quality epoxy resin material and has five (5) #8-32 screw terminals.
Check Inventory

Specifications
Control Voltage:24 or 120 VAC, ±10%, 50/60 Hz
Control Switch:Open Circuit Voltage: 16 VDC
Short Circuit Current: 200 uAmps
Contact Rating:SPST-N.O., 10 amps @ 24 or 120 VAC, Resistive
278 VA, Inductive
Isolation:2500 volts, Input to Output
Power Required:1.5 VA
Temperatures:Operate: –20°C to +55°C
Storage: –40°C to +85°C
Response Times:Operate: 6 mSeconds (Approx.)
Release: 2.5 mSeconds (Approx.)
Life Expectancy:Mechanical: 20 Million Operations
Electrical: 50,000 Operations @ Rated Load
Duty Cycle:Continuous
LED Indicator:On When Output is On
Agency Approvals:UL913 File #E151578; Class I, Groups A, B, C, D; Class II, Groups E, F, G; Class III, Hazardous Locations in ATC-DE; Drawing Nos. 191, 192


How To Order


Items shown on this page represent only our stocking items.
If you don't find what you are looking for, please give us a call.
Prices subject to change without notice.



FastCounter by bCentral