| IN STOCK SERIES: | |
|---|---|
| DELAY ON MAKE RELAYS | SINGLE SHOT TIME DELAY |
| A1K SERIES TIME DELAY | Q2F SERIES |
| A1M SERIES MULTI-RANGE | T2 SERIES |
| CKK SERIES TIME DELAY REPEAT CYCLE | MULTI-TIME RANGE/FUNCTION TIME DELAY |
| K1K SERIES TIME DELAY | DMM SERIES FLATPAK (INPUT VOLTAGE) |
| Q1D SERIES TIME DELAY SERIES LOAD | TMM SERIES TIMER |
| Q1F SERIES TIME DELAY SERIES LOAD | 1/16 DIN TMM SERIES (INPUT VOLTAGE) |
| Q1T SERIES TIME DELAY SERIES LOAD | DELAY ON BREAK TIME DELAY RELAYS |
| T1 SERIES DELAY | T3 SERIES RETRIGGERABLE |
| FLASHER TIME DELAY RELAYS | T3M SERIES MULTI-RANGE RETRIGGERABLE |
| Q8F SERIES | Q3F SERIES RETRIGGERABLE |
| INTERVAL TIME DELAY RELAYS | SOLID STATE RELAYS |
| Q4F SERIES | R2025 SERIES (SNC-) |
| T7 SERIES DELAYED | Don't see the series you need? Give us a call! 800-877-8919 |
| Q4T SERIES RELAY OUTPUT | |

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay | Adjustment: Knobs, factory fixed on special order (min. order required) | Range: 50 mS to 10 hours in 14 ranges |
| Repeatability: ± 1% at constant temperature | Accuracy: max. time -0%, + 10%; min. time +0%, -50% | |
| Reset Time: 500 milliseconds max. | ||
| Input | Operating Voltage: 12, 24 VDC; 24, 120 VAC ± 10% (D.C. models have reverse polarity protection. Unfiltered input voltage to them must be full-wave rectified) | Power Consumption: 3 VA max. |
| Frequency: 50/60 Hz | ||
| Output | Type: Relay D.P.D.T. (2 form C) Silver Cad. Oxide material | Rating: 10 amp. max. resistive at 240 volts A.C.; 100 mA at 5 VDC min. Load current |
| Life: Mechanical -10,000,000 operations Full Load - 500,000 operations | ||
| Protection | Transient Voltage: 12 and 24 volt timers are protected by an 8.8 joule metal oxide varistor 120 volt timers are protected by a 30 joule metal oxide varistor | Dielectric Breakdown: 1500 volts RMS min. at 60 Hz between input and outputs and between outputs |
| Mechanical | Termination: 8-pin plug | Mounting: Socket Mount - Part Number MSO-0008P-012 |
| Environmental | Storage Temperature: -23°C to 70°C | Operating Temperature: -23°C to 55°C |

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: 3-digit pushbutton switch | Range: 50 mS to 999 minutes in 5 ranges |
| Repeatability: ± 0.1%, ± 20 mS over specified timing range | Accuracy: ± 1% of set time, plus fixed error of 80 mS max. (40 mS typical including power on response time) | |
| Input: | Operating Voltage: 24, 120, 240 VAC, 12, 24 VDC ± 10% (D.C. models have reverse
polarity protection. Unfiltered input voltage to them must be full-wave rectified) | Power On Response: 50 mS max. |
| Power Off Reset Time: 150 mS min. | Start Switch Closure Time: 200 mS to initiate timing cycle 50 mS to reset delay during cycle | |
| Power Consumption: 2 VA max. | Frequency: 50/60 Hz | |
| Output: | Type: Relay Contacts, D.P.D.T. (2 form C) Silver Cad. Oxide material | Rating: 10 amp. max. resistive at 240 volts A.C. 100 mA at 5 VDC min. load current |
| Life: Mechanical - 10,000,000 operations Full Load - 500,000 operations | Timing Light Logic: Flashing during timing; continuously on after time out | |
| Protection: | Transient Voltage: 12, 24 volt timers are protected by an 8.8 joule metal oxide
varistor 120, 240 volt timers are protected by a 30 joule metal oxide varistor. | Dielectric Breakdown: 1500 VAC RMS min. at 60 Hz between input and outputs and between outputs. |
| Mechanical: | Termination: 8 - pin plug | Mounting: Socket Mount - Part No. MSO-0008P-012 |
| Environmental: | Storage Temperature: -23°C to 70°C | Operating Temperature: -23°C to 55°C |
| Humidity: 95% relative | ||
| Timing: | Selectable Time Ranges: .05 to 9.99 seconds .1 to 99.9 seconds 1 to 999 seconds.1 to 99.9 minutes 1 to 999 minutes (Times less than 50 mS are not recommended due to the response time of the mechanical relay) | |
| Programming: | To program the timer, remove power from the unit and select the time range, use the digital switches to select the required time (0-999) | |

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: Knob, factory fixed on special order (min. order required) | Range: 50 mS to 10 hours in 15 ranges |
| Repeatability: ±1% at constant temperature | Accuracy: max. time -0%, +10%; Midpoint of Dial ± 5%; min. time +0%, -50% | |
| Input: | Operating Voltage: 120 volt A.C. ± 10% | Power Consumption: 3 VA max. |
| Frequency: 50/60 Hz | ||
| Output: | Type: Relay Contacts, D.P.D.T. (2 form C) Silver Cad. Oxide material | Rating: 10 amp. max. resistive at 240 volts A.C.; 100 mA at 5 VDC min. load current |
| Life: Mechanical -10,000,000 operations Full Load - 500,000 operations | ||
| Protection: | Transient Voltage: Timers are protected by a 30 joule metal oxide varistor | Dielectric Breakdown: 1500 VAC, RMS min. at 60 Hz between input and outputs and between outputs |
| Timing Light Logic: On during timing; Off after time out | ||
| Mechanical: | Termination: 8-pin plug | Mounting: Socket Mount - Part Number MSO-0008P-012 |
| Environmental: | Storage Temperature: -23°C to 70°C | Operating Temperature: -23° to 55°C |

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: 3 digit pushbutton switch | Range: 50 mS to 999 hours in 6 ranges |
| Repeatability: ± 0.1% of set time or ± 20 mS whichever is greater. | Accuracies: All Functions . . ± 1% of set time or ± 20 mS whichever is greater. | |
| Input: | Operating Voltage:24 - 240VAC ± 15%, 50/60 Hz;24 - 240VDC ± 15%, (DC Unfiltered input voltage must be full-wave rectified) | Power On Response: 50 mS max. |
| Power Off Reset Time: Requires power interruption of 150mS max. (50 mS typ.) | Start Switch Closure Time: 50 mS. min. to initiate timing cycle; 50 mS. min.to reset delay during timing cycle | |
| Power Consumption: 14 VA max. at 276 VAC, 2.5 VA max.at 24 VAC | ||
| Output | Type: Relay D.P.D.T. (2 form C) Silver Cad. Oxide material | Rating: 10 amp. max. resistive at 240 VAC, 125VDC 1/2 HP at 240 VAC 10 mA at 5 VDC min. Load current |
| Life: Mechanical - 10,000,000 operations Full Load - 500,000 operations | ||
| Environmental: | Storage Temperature: -25°C to 70°C | Operating Temperature: -25° to 55°C |
| Humidity: 95% relative | ||
| Mechanical: | Termination: 6 screw terminalsPermissible wire size: 22-12 gauge | Mounting: 35mm DIN Rail mount NCC P/N for 3 foot section of 35 mm rail: MRL-SOCKT-011 Note: The DMM Series also mounts on 7.5mm and 15mm rails. |
| Protection: | Transient Voltage: 30 joule, 250 volt metal oxide varistor | Dielectric Breakdown: 1800 VAC, RMS min. at 60 Hz between input and outputs and between outputs |
| Timing Light Logic: | Repeat Cycle: Full On during "Off" time; Flashing during "On" time | Other Logic Modes: Flashing during timing; Full On after time out |
| Timing: | Selectable Time Ranges: .05 to 9.99 seconds .1 to 99.9 seconds 1 to 999 seconds .1 to 99.9 minutes 1 to 999 minutes 1 to 999 hours (Times less than 50 mS are not recommended due to the response time of the mechanical relay) | |
| Selectable Operating Logic Modes: | Repeat Cycle (50% fixed duty cycle) Single Shot (1 shot) Delay On Break (D.O.B.) Interval (Intervl) Delay On Make (D.O.M.) | |
| Programming: | To program the timer, remove voltage from the unit and select the operating logic mode and the time range; use the digital switches to select the required time (0-999) | |

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: Knob or external resistor, factory fixed on special order (min. order required) | Range: 100 mS to 10 minutes in 9 ranges * |
| Repeatability: ± .5% at constant temperature and reset time, but not less than 16 mS. | Accuracy: Max. Time +(10%, +20mS) / -0% Min. Time -50% / +(0%, +20mS) | |
| Reset Time: 80 milliseconds max. | ||
| Input: | Operating Voltage: 24, 120 VAC;12, 24 VDC ± 10% (D.C. models have reverse polarity protection. Unfiltered input voltage to them must be full-wave rectified) | Power Consumption: 3 VA max. |
| Frequency: 50/60 Hz (AC Units) | ||
| Output: | Type: Relay Contacts, D.P.D.T. (2 form C) Silver Cad. Oxide material | Rating: 10 amp. max. resistive at 240 VAC; 100 mA at 5 VDC min. load current |
| Life: Mechanical - 1,000,000 operations Full Load -150,000 operations | ||
| Protection: | Transient Voltage: 12 & 24 volt timers are protected by a 1 joule metal oxide varistor; 120 & 240 volt timers are protected by a 5 joule metal oxide varistor. | Dielectric Breakdown: 1500 VAC, RMS min. at 60 Hz between input and outputs and between outputs |
| Mechanical: | Termination: Spade (.187"x.020" terminal) type plug-in base | Mounting: Socket Mount - Part Number MSO-00KUP-012 or Flange Mount |
| Environmental: | Storage Temperature: -23°C to 70°C | Operating Temperature: -23°C to 55°C |
| *Due to a redesigned digital timing circuit, the K1 Series now offers a greater time range capability; up to 10 hours. Consult factory for details. | ||

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: 10 Position DIP switch. | Range: 1 to 1023 seconds in one second increments. Zero time setting is undefined. |
| Repeatability: ± 0.5% (0.25% typ) at constant temperature. | Accuracy: ± 10% of set time +0 .25 second. | |
| Input: | Operating Voltage: 24 to 240 VAC/DC ±10% (On DC models, unfiltered supply voltage must be full-wave rectified) | Frequency: 50/60 Hz |
| Output: | Type: Solid-state, normally open series load | Rating: 1 amp. steady state max. |
| Life: 100,000,000 operations | ||
| Protection: | Transient Voltage: 30 Joule Metal oxide varistor | Dielectric Breakdown: 3000 VAC, RMS, terminals to mounting |
| Insulation Resistance: 100 megohms min. between terminals and case | ||
| Mechanical: | Termination: .25" x .032" male fast-on terminals | Mounting: Surface mount with one #8 screw |
| Environmental: | Storage Temperature: -40°C to 85°C | Operating Temperature: -40° to 85°C |
| Humidity: 95% relative | ||

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: External resistor, factory fixed on special order (min. order requirement) | Range: 50 mS to 10 hours in 9 ranges increments. |
| Repeatability: ±.5% + 8 mS max. (0.25% typ) at constant temperature | Accuracy: max. time ±2% at Rt = 1 megohms; min. time +0%, -30% at Rt = 0 ohm | |
| Input: | Operating Voltage: 12, 24, 120, 240 VAC/DC ±10% (On DC models, unfiltered supply voltage must be full-wave rectified) | Frequency: 50/60 Hz |
| Output: | Type: Solid-state, normally open series load | Rating: 1 amp. steady state max. |
| Life: 100,000,000 operations | ||
| Protection: | Transient Voltage: Metal oxide varistor | Dielectric Breakdown: 3000 VAC, RMS, terminals to mounting |
| Insulation Resistance: 100 megohms min. between terminals and case | ||
| Mechanical: | Termination: .25" x .032" male fast-on terminals | Mounting: Surface mount with one #8 screw |
| Environmental: | Storage Temperature: -40°C to 85°C | Operating Temperature: -40° to 85°C |
| Humidity: 95% relative | ||

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: On-board trimpot | Range: 50 mS to 10 hours in 9 ranges |
| Repeatability: ±..5% + 8 mS max. (0.25% typ) at constant temperature | Accuracy: max. time -0%, +10% min. time -30%, +0% | |
| Input: | Operating Voltage: 12, 24, 120, 240 VAC/DC ±10% (On DC models, unfiltered supply voltage must be full-wave rectified) | Frequency: 50/60 Hz |
| Output: | Type: Solid-state, normally open series load | Rating: max. Current -1 amp. AC/DC (resistive or inductive) |
| Life: 100,000,000 operations | ||
| Protection: | Transient Voltage: Metal oxide varistor | Dielectric Breakdown: 3000 VAC, RMS, terminals to mounting |
| Isolation Resistance: 100 megohms min. between terminals and case | ||
| Mechanical: | Termination: .25" x.032" male fast-on terminals | Mounting: Surface mount with one #8 screw |
| Environmental: | Storage Temperature: -40°C to 85°C | Operating Temperature: -40°C to 65°C |
| Humidity: 95% relative | ||

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: External resistor factory fixed on special order (min. order requirement) | Range: 50 mS to 10 hours in 9 ranges |
| Repeatability: ±.5% + 8 mS max. (0.25% typ) at constant temperature | Accuracy: max. time ±2% at Rt = 1 megohmsmin. time +0%, -30 % at Rt = 0 ohm | |
| Input: | Operating Voltage: 120, 240 VAC; 12 VDC; 24 VAC/DC ± 10% (D.C. models have reverse polarity protection. Unfiltered input voltage to them must be full-wave rectified) | Frequency: 50/60 Hz |
| Output: | Type: Solid-state, normally open | Rating: 1 amp. steady state |
| Life: 100,000,000 operations | ||
| Protection: | Transient Voltage: Metal oxide varistor | Dielectric Breakdown: 3000 VAC, RMS, terminals to mounting |
| Insulation Resistance: 100 megohms min. between terminals and case | ||
| Mechanical: | Termination: .25" x .032" male fast-on terminals | Mounting: Surface mount with one #8 screw |
| Environmental: | Storage Temperature: -40°C to 85°C | Operating Temperature: -40°C to 65°C |
| Humidity: 95% relative | ||

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: External resistor, factory fixed on special order (min. order requirement) | Range: 50 mS to 10 hours in 9 ranges |
| Repeatability: ±..5% + 8 mS max. (0.25% typ) at constant temperature | Accuracy: max. time ±2% at Rt = 1 megohm min. time +0%-30% at Rt = 0 ohm | |
| Input: | Operating Voltage: 120, 240 VAC; 12 VDC; 24 VAC/DC ±10% (D.C. models have reverse polarity protection. Unfiltered input voltage to them must be full-wave rectified) | Frequency: 50/60 Hz |
| Output: | Type: Solid-state, normally open | Rating: 1 amp. steady state |
| Life: 100,000,000 operations | ||
| Protection: | Transient Voltage: Metal oxide varistor | Dielectric Breakdown: 3000 VAC, RMS, terminals to mounting |
| Isolation Resistance: 100 megohms min. between terminals and case | ||
| Mechanical: | Termination: .25" x .032" male fast-on terminals | Mounting: Surface mount with one #8 screw |
| Environmental: | Storage Temperature: -40°C to 85°C | Operating Temperature: -40°C to 65°C |
| Humidity: 95% relative | ||

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: External resistor, factory fixed on special order (min. order requirement) | Range: 50 mS to 10 hours in 9 ranges |
| Repeatability: ±.5% + 8 mS max. (.25% typ) at constant temperature | Accuracy: max. time ±2% at Rt = 1 megohms min. time +0%, -30% at Rt = 0 ohm | |
| Input: | Operating Voltage: 120, 24 VAC/DC ±10%; (D.C. models have reverse polarity protection. Unfiltered input voltage to them must be full-wave rectified) | Frequency: 50/60 Hz |
| Output: | Type: Solid-state, normally open | Rating: 1 amp steady state |
| Life: 100,000,000 operations | ||
| Protection: | Transient Voltage: Metal oxide varistor | Dielectric Breakdown: 3000 VAC, RMS, terminals to mounting |
| Insulation Resistance: 100 megohms min. between terminals and case | ||
| Mechanical: | Termination: .25"x.032" male fast-on terminals | Mounting: Surface mount with one #8 screw |
| Environmental: | Storage Temperature: -40°C to 85°C | Operating Temperature: -40°C to 65°C |
| Humidity 95% relative | ||

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: On-board trimpot | Range: 50 mS to 10 hours in 9 ranges |
| Repeatability: ±0.5% max. (0.25% typical) at constant temperature | Accuracy: max. time +10%, -0% min. time -30%, +0% | |
| Reset Time: 250 mS max., by removal of the input voltage | ||
| Input: | Operating Voltage: 120 volts A.C. ± 10% | Power Consumption:3.5 VA max. |
| Frequency: 50/60 Hz | ||
| Output: | Type: Relay Contacts, S.P.D.T. (1 form C) Silver Cad. Oxide material | Rating: 8 amp. max. resistive at 250 VAC & 30 VDC; 100 mA at 5 VDC min. load current |
| Life: Mechanical: -10,000,000 cycles | Electrical: -100,000 min. at full load | |
| Protection: | Transient Voltage: 1000 P.I.V. components used | Isolation Resistance: 100 megohms min. between terminals and case |
| Dielectric Breakdown: 3000 VAC, RMS, terminals to mounting; 1500 VAC, RMS, input to output; | ||
| Mechanical: | Termination: .25"x.032" male fast-on terminals | Mounting: Surface mount with one #8 screw |
| Environmental: | Storage Temperature: -40°C to 70°C | Operating Temperature: -40°C to 70°C |
| Humidity: 95% relative | ||

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: Knob, factory fixed on special order (min. order required) | Range: 50 mS to 1 hour in 10 ranges |
| Repeatability: ± 1% at constant temperature | Accuracy: max. time -0%, +10%; min. time +0%, -50% | |
| Reset Time: 50 milliseconds max. | ||
| Input: | Operating Voltage: 24, 120 VAC; 12, 24 VDC ± 10% (D.C. models have reverse polarity protection. Unfiltered input voltage to them must be full-wave rectified) | Power Consumption: 3 VA max. |
| Frequency: 50/60 Hz | ||
| Output: | Type: Relay Contacts, D.P.D.T. (2 form C) Silver Cad. Oxide material | Rating: 10 amp. max. resistive at 240 volts A.C 100 mA at 5 VDC min. Load current |
| Life: Mechanical -10,000,000 operations Full Load - 500.000 operations | ||
| Protection: | Transient Voltage: 12 and 24 volt timers are protected by an 8.8 joule metal oxide varistor; 120 volt timers are protected by a 30 joule metal oxide varistor | Dielectric Breakdown: 1500 VAC, RMS min. at 60 Hz between input and outputs and between outputs |
| Mechanical: | Termination: 8-pin plug-in base | Mounting: Socket Mount - Part Number MSO-0008P-012 |
| Environmental: | Storage Temperature: -23°C to 70°C | Operating Temperature: -23°C to 55°C |

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: Knob, factory fixed on special order (min. order required) | Range: 50 mS to 1 hour in 11 ranges |
| Repeatability: ±1% at constant temperature | Accuracy: max. time -0%, +10%; min. time +0%, - 50% | |
| Reset Time: 400 milliseconds max. | ||
| Input: | Operating Voltage: 24, 120 VAC; 12, 24 VDC ± 10% (D.C. models have reverse polarity protection. Unfiltered input voltage to them must be full-wave rectified) | Start Switch Closure Time: 20 milliseconds min. |
| Power Consumption: 3 VA max. | Frequency: 50/60 Hz | |
| Output: | Type: Relay Contacts, S.P.D.T. (1 form C) or D.P.D.T. (2 form C) Silver Cad. Oxide material | Rating: 10 amp. max. resistive at 240 volts A.C.; 100 mA at 5 VDC min. load current |
| Life: Mechanical -10,000,000 operationsFull Load - 500,000 operations | ||
| Protection: | Transient Voltage: 12 and 24 volt timers are protected by an 8.8 joule metal oxide varistor; 120 volt timers are protected by a 30 joule metal oxide varistor | Dielectric Breakdown: 1500 VAC, RMS min. at 60 Hz between input and outputs and between outputs |
| Mechanical: | Termination: 8-pin or 11-pin plug | Mounting: Socket Mount - 8-Pin Part Number MSO-0008P-012Socket Mount -11-Pin Part Number MSO-0011P-012 |
| Environmental: | Storage Temperature: -23°C to 70°C | Operating Temperature: -23°C to 55°C |

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: Knob, factory fixed on special order (min. order required) | Range: 50 mS to 1 hour in 11 ranges |
| Repeatability: ±1% at constant temperature | Accuracy: max. time -0%, +10% min. time +0%. -50% | |
| Reset Time: 400 milliseconds max. | Start Switch Closure Time: 20 mS to initiate timing; 50 mS to reset delay during timing | |
| Input: | Operating Voltage: 24, 120 VAC; 12, 24 VDC ±10% (D.C. models have reverse polarity protection. Unfiltered input voltage to them must be full-wave rectified) | Power Consumption: 3 VA max. |
| Frequency: 50/60 Hz | ||
| Output: | Type: Relay Contacts, S.P.D.T. (1 form C) or D.P.D.T. (2 form C) Silver Cad. Oxide material | Rating: 10 amp. max. resistive at 240 volts A.C.; 100 mA at 5 VDC min. Load current |
| Life: Mechanical -10,000,000 operations Full Load - 500,000 operations | ||
| Protection: | Transient Voltage: 12 and 24 volt timers are protected by an 8.8 joule metal oxide varistor; 120 volt timers are protected by a 30 joule metal oxide varistor | Dielectric Breakdown: 1500 VAC, RMS min. at 60 Hz between input and outputs and between outputs |
| Mechanical: | Termination: 8-pin or 11-pin plug | Mounting: Socket Mount - 8-Pin Part Number MSO-0008P-012 Socket Mount -11-Pin Part Number MSO-0011P-012 |
| Environmental: | Storage Temperature: -23°C to 70°C | Operating Temperature: -23°C to 55°C |

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: 3 digit pushbutton switch | Range: 50 mS to 999 minutes in 5 ranges |
| Repeatability: ± 0.1%, ± 20 mS over specified timing range | Accuracy:±1% of set time, plus fixed error of 75 mS max. (10 mS typical) | |
| Power On Response Time: 50 mS max. | Power Off Reset Time: Requires power interruption of 150 mS min. | |
| Start Switch Closure Time: 20 mS to initiate timing cycle; 50 mS to reset delay during timing cycle | Input Operating Voltage: 24, 120 VAC; 12, 24 VDC ±10% (D.C. models have reverse polarity protection. Unfiltered input voltage to them must be full-wave rectified) | |
| Power Consumption: 2 VA max. | Frequency: 50/60 Hz | |
| Output: | Type: Relay Contacts, D.P. D.T. (2 form C) Silver Cad. Oxide material | Rating: 10 amp. max. resistive at 240 volts A.C.; 100 mA at 5 VDC min. load current |
| Life: Mechanical -10,000,000 operations Full Load - 500,000 operations | ||
| Protection: | Transient Voltage: 12 and 24 volt timers are protected by an 8.8 joule metal oxide varistor; 120 volt timers are protected by a 30 joule metal oxide varistor | Dielectric Breakdown: 1500 VAC, RMS min. at 60 Hz between input and outputs and between outputs |
| Timing Light Logic: Flashing during timing; Full On after time out | ||
| Mechanical: | Termination: 11-pin plug | Mounting: Socket Mount - Part Number MSO-0011P-012 |
| Environmental: | Storage Temperature: -23°C to 70°C | Operating Temperature: -23°C to 55°C |
| Humidity: 95% relative | ||
| Timing: | Selectable Time Ranges: .05 to 9.99 seconds .1 to 99.9 seconds1 to 999 seconds.1 to 99.9 minutes1 to 999 minutes(Times less than 50 mS are not recommended due to the response time of the mechanical relay) | |

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: Knob, factory fixed on special order (min. order required) | Range: 50 mS to 10 hours in 9 ranges |
| Repeatability: ± 1% at constant temperature | Accuracy: max. time -0%, +10%; min. time +0%, -50% | |
| Reset Time: 150 milliseconds max. | ||
| Input: | Operating Voltage: 120 VAC ± 10% | Power Consumption: 3 VA max. |
| Frequency: 50/60 Hz | ||
| Output: | Type: Relay D.P.D.T. (2 form C) Silver Cad. Oxide material | Rating: 10 amp. max. resistive at 240 volts A.C.; 100 mA at 5 VDC min. Load current |
| Life: Mechanical -10,000,000 operations Full Load - 500,000 operations | ||
| Protection: | Transient Voltage: timer is protected by a 30 joule metal oxide varistor | Dielectric Breakdown: timer is protected by a 30 joule metal oxide varistor |
| Mechanical: | Termination: 8-pin plug | Mounting: Socket Mount - Part Number MS0-0008P-012 |
| Environmental: | Storage Temperature: -23°C to 70°C | Operating Temperature: -23°C to 55°C |

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: External resistor, factory fixed on special order (min. order requirement) | Range: 50 mS to 5 minutes in 5 ranges |
| Repeatability: ± .5% + 8 mS max. (0.25% typ) at constant temperature | Accuracy: max. time ±2% at Rt = 1 megohms min. time +0%, -30% at Rt = 0 ohm | |
| Input: | Operating Voltage: 120 VAC ±10% | Frequency: 50/60 Hz |
| Output: | Type: Solid-state, normally open | Rating: 1 amp. steady state |
| Life: 100,000,000 operations | ||
| Protection: | Transient Voltage: Metal oxide varistor | Dielectric Breakdown: 3000 VAC, RMS, terminals to mounting |
| Insulation Resistance: 100 megohms min. between terminals and case | ||
| Mechanical: | Termination: .25"x .032" male fast-on terminals | Mounting: Surface mount with one #8 screw |
| Environmental: | Storage Temperature: -40°C to 85°C | Operating Temperature: -40°C to 65°C |
| Humidity 95% relative | ||

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: 3 digit pushbutton switch | Range: 50 mS to 999 minutes in 5 ranges |
| Repeatability: ± 0.1%, ± 20 mS over specified timing range. | ||
| Accuracies: | Delay On Make. . . ± 1% of set time, plus fixed error of 80 mS max. (40 mS typical including power-on response time) | Interval, One-Shot. . . ± 1% of set time, plus fixed error of 35 mS max. (10 mS typical) |
| Delay On Break. . . ±1% of set time, plus fixed error of 75 mS max. (10 mS typical) | Repeat Cycle, On Time. . . ± 1% of set time, plus fixed error of 35 mS max. (10 mS typical) | |
| Repeat Cycle, Off Time. . . ± 1% of set time, minus error of 65 mS max. (10 mS typical) | ||
| Input: | Operating Voltage: 24, 120, 240 VAC; 12, 24, 48 VDC ± 10% (D.C. models have reverse polarity protection. Unfiltered input voltage to them must be full-wave rectified) | Power On Response: 50 mS max. |
| Power Off Reset Time: 150 mS. min. | Start Switch Closure Time: 20 mS. to initiate timing cycle; 50 mS to reset delay during timing cycle | |
| Power Consumption: 2 VA max. | Frequency: 50/60 Hz | |
| Output: | Type: Relay D.P.D.T. (2 form C) Silver Cad. Oxide material | Rating: 10 amp. max. resistive at 240 volts A.C.; 10 mA at 5 VDC min. Load current |
| Life: Mechanical - 10,000,000 operationsFull Load - 500,000 operations | ||
| Timing Light Logic: | Repeat Cycle: Flashing during "On" time; Full On during "Off" time | Other Logic Modes: Flashing during timing; continuously on after time out |
| Protection: | Transient Voltage: 12, 24, 48 volt timers are protected by an 8.8 joule metal oxide varistor; 120, 240 volt timers are protected by a 30 joule metal oxide varistor. | Dielectric Breakdown: 1500 VAC, RMS min. at 60 Hz between input and outputs and between outputs. |
| Mechanical: | Termination: 11-pin plug | Mounting: Socket Mount - Part Number MSO-0011P-012 |
| Environmental: | Storage Temperature: -23°C to 70°COperating Temperature: -23° to 55°C | Humidity: 95% relative |
| Timing: | Selectable Time Ranges:.05 to 9.99 seconds .1 to 99.9 seconds 1 to 999 seconds .1 to 99.9 minutes 1 to 999 minutes (Times less than 50 mS are not recommended due to the response time of the mechanical relay) | Selectable Operating Logic Modes: Repeat Cycle (50% fixed duty cycle) Single Shot (1 shot) Delay On Break (D.O.B.) Interval (Intervl) Delay On Make (D.O.M.) |
| Programming: | To program the timer, remove voltage from the unit and select the operating logic mode and the time range, use the digital switches to select the required time (0-999) | |
| Note: 1) Do not apply voltage or ground to the Start switch, 2) Switch leads should be shielded when running close to other wires (Start switch supplied by customer) | ||

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: 3 digit pushbutton switch | Range: 50 mS to 999 minutes in 6 ranges |
| Repeatability: ± 0.1% of set time or ± 20 mS whichever is greater. | Accuracies: All Functions: ± 1% of set time or ± 20 mS whichever is greater. | |
| Input: | Operating Voltage: 24 - 240VAC ± 15%, 50/60 Hz; 24 - 240VDC ± 15%, (DC Unfiltered input voltage must be full-wave rectified) | Power On Response: 50 mS max. |
| Power Off Reset Time: Requires power interruption of 150 mS. max. (50 mS typ.) | Start Switch Closure Time: 20 mS. min. to initiate timing cycle; 50 mS min. to reset delay during timing cycle | |
| Power Consumption: 14 VA max. at 276 VAC; 2.5 VA max. at 24 VAC | ||
| Output: | Type: Relay D.P.D.T. (2 form C) Silver Cad. Oxide material | Rating: 10 amp. max. resistive at 240 VAC; 125 VDC 1/2 HP at 240 VAC 10mA at 5 VDC min. Load current |
| Life: Mechanical - 10,000,000 operations Full Load - 500,000 operations | ||
| Protection: | Transient Voltage: 30 joule, 250V metal oxide varistor. | Dielectric Breakdown: 1800 VAC, RMS min. at 60 Hz between input and outputs and between outputs. |
| Mechanical: | Termination: 11-pin plug or spade type | Mounting: Back Panel Mount: Spade Base use MSO-0000KUP-012; Pin Base use MSO-011P-012 Front Panel Mounting: (1.78" sq. opening required) Front Panel Mounting Bracket MBK-1/16D-011 11 Pin Base use MSO-0011P-013 |
| Environmental: | Storage Temperature: -25°C to 70°C | Operating Temperature: -25° to 55°C |
| Humidity: 95% relative | ||
| Timing: | Selectable Time Ranges:.05 to 9.99 seconds .1 to 99.9 seconds 1 to 999 seconds .1 to 99.9 minutes 1 to 999 minutes 1 to 999 hours (Times less than 50 mS are not recommended due to the response time of the mechanical relay) | Selectable Operating Logic Modes: Repeat Cycle (50% fixed duty cycle) Single Shot (1 shot) Delay On Break (D.O.B.) Interval (Intervl) Delay On Make (D.O.M.) |
| Programming: | To program the timer, remove voltage from the unit and select the operating logic mode and the time range, use the digital switches to select the required time (0-999) | |
| Note: 1) Do not apply voltage or ground to the Start switch 2) Switch leads should be shielded when running close to other wires (Start switch supplied by customer) | ||

| SPECIFICATIONS: | ||
|---|---|---|
| Time Delay: | Adjustment: Knob or external resistor, factory fixed on special order (min. order required) | Range: 50 mS to 10 hours in 16 ranges |
| Repeatability: ± 1% at constant temperature | Accuracy: max. time -0%, +10%; min. time +0%, -50% | |
| Reset Time: 50 mS max. (25 mS typical) | ||
| Input: | Operating Voltage: 24, 120, 240 VAC; 12, 24 VDC ± 10% (D.C. models have reverse polarity protection. Unfiltered input voltage to them must be full-wave rectified). | Power Consumption: 3 VA max. |
| Frequency: 50/60 Hz | ||
| Output: | Type: Relay Contacts, D.P.D.T. (2 form C) Silver Cad. Oxide material | Rating: 10 amp. max. resistive at 240 volts A.C.; 100 mA at 5 VDC min. load current |
| Life: Mechanical -10,000,000 operations Full Load - 500,000 operations | ||
| Protection: | Transient Voltage: 12, 24 volt timers are protected by an 8.8 joule metal oxide varistor; 120, 240 volt timers are protected by a 30 joule metal oxide varistor | Dielectric Breakdown: 1500 VAC, RMS min. at 60 Hz between input and outputs and between outputs |
| Mechanical: | Termination: 8-pin or 11-pin plug | Mounting: Socket Mount- 8-Pin Part Number MSO-0008P-012Socket Mount- 11-Pin Part Number MSO-0011P-012 |
| Environmental: | Storage Temperature: -23°C to 70°C | Operating Temperature: -23° to 55°C |

| IN STOCK MODEL SPECIFICATIONS: | ||
|---|---|---|
| P/N | SNC-R2025-501 | SNC-R2025-507 |
| Max. Load Current | 25 Amps | |
| Max. Surge Current | 370 Arms, 8.3mS | |
| Max. On State Voltage Drop | 1.65 VAC (RMS) | 1.5 VAC (RMS) |
| Min. Off State dv/dt (static) | 500V/µS | |
| Thermal Resistance Junction to Case (point A) | 1.3 °C/Watt Tj max.=110 °C | |
| Input Impedance | 56 Kohms ±5% | 1700 ohms ±5% |
| Turn Off Voltage | 30 VAC max. | 2 VAC/DC max. |
| Turn On Voltage | 70 VAC max. | 3 VAC/DC min. |
| Turn On Type | Random | |
| Output Form | S.P.S.T.-N.O. | |
| Control Voltage Range | 70-140 VAC | 3-30 VAC/DC |
| General Specifications (all models available in the R2010 thru R2040 Series) | |||||
|---|---|---|---|---|---|
| Max. Load Current * | 10 Amps | 25 Amps | 25 Amps | 25 Amps | 40 Amps |
| Model Numbers | SNC-R2010-502 SNC-R2010-505 | SNC-R2025-502 SNC-R2025-505 | SNC-R2025-501 SNC-R2025-507 | SNC-R2025-511 SNC-R2025-517 | SNC-R2040-502 SNC-R2040-505 |
| Max. Peak Transient Voltage | 600 Vpk | ||||
| Output Voltage Range | 24-330 VAC | 48-300 VAC | 24-330 VAC | ||
| Max. Off State Leakage Current | 8 mA @330 VAC (RMS) | 7.2 mA @300 VAC (RMS) | 8 mA @330 VAC (RMS) | ||
| Operating Temp. Range | -40 to 100 °C | -40 to 80 °C | -40 to 100 °C | ||
| Storage Temp. Range | -40 to 100 °C | -40 to 65 °C | -40 to 100 °C | ||
| Dielectric Strength @60 Hz | |||||
| between Input / Output | 4000 VAC (RMS) | ||||
| between Input / Base | 4000 VAC (RMS) | 2500 VAC (RMS) | 4000 VAC (RMS) | ||
| between Output / Base | 4000 VAC (RMS) | 2500 VAC (RMS) | 4000 VAC (RMS) | ||